壓縮機工作時,空氣經過自潔式空氣過濾器被吸入,通過PLC自動清洗過濾器,空氣在經過進口導葉自動調節后進入一級壓縮,經一級壓縮后的氣體溫度較高,然后進入中間冷卻器進行冷卻(水走管內,氣走管外,中冷器的水流量要求為110m/h)之后進入二級壓縮系統,為避免系統中的氣體倒入壓縮腔內(避免帶壓起動)在壓縮機的排氣管道安裝有一只懸掛全啟式止回閥,壓縮機排出的氣體推開止回閥進入排氣消聲器,然后進入一級后冷器,二級后冷器,再進入排氣主管道。
When the compressor works, the air is absorbed through the self-cleaning air filter, and the filter is automatically cleaned by PLC. After the air is automatically adjusted by the inlet guide vane, it enters the first stage compression. After the first stage compression, the gas temperature is higher. Then it enters the intermediate cooler for cooling (water running in the pipe, outside the gas running in the pipe, water flow of the intercooler is www.xiekou.net.cn www.wantou.net.cn www.buxiugangdai.net.cn www.zhenkongdiaoju.cn www.goucaoguanjia.cn www.kagu.org.cnrequired to be 110 m/h), and then enters the second stage compression system. In order to avoid the gas in the system pouring into the compression chamber (avoid starting with pressure), a hanging full-open check valve is installed in the exhaust pipe of the compressor. The gas discharged by the compressor pushes the check valve into the exhaust muffler, and then enters the first-stage rear cooler, the second-stage rear cooler and the exhaust main pipe.
3:水路循環系統
3: Water circulation system
冷卻水通過管道進入空壓機中間冷卻器對一級壓縮排出的氣體進行冷卻降溫,再進入后冷器對排氣進行冷卻,另一路冷卻水進水管道經過主電機上部的兩組換熱器冷卻電機繞組,還有一路對油冷卻器進行冷卻。
Cooling water enters the air compressor intermediate cooler through pipes to cool the first compressed exhaust gas, and then enters the rear cooler to cool the exhaust gas. Another cooling water inlet pipe passes through two sets of heat exchangers on the upper part of the main motor to cool the motor windings, and another way to cool the oil cooler.
4:配電系統
4: Distribution System
空壓機為2000kW高壓電機(10kV)采用全壓啟動,控制柜為戶內交流、金屬鎧裝抽出式開關設備,開關設備由固定的柜體和可抽出部件即手車兩大部分組成,實現控制、保護、監測的目的,具有“五防”功能。
The air compressor is a 2000 kW high-voltage motor (10kV) with full-voltage start-up. The control cabinet is an indoor AC and metal armoured pull-out switchgear. The switchgear consists of a fixed cabinet body and a pull-out component, i.e. a handcart. It realizes the purpose of control, protection and monitoring, and has the function of "five preventions"